| Input Voltage |
85 ~ 264Vac 20 ~ 370Vdc |
| Input Frequency |
47 ~ 63Hz |
| Input Current |
0.55A/115Vac 0.35A/230Vac |
| Inrush Current |
20A/115Vac 40A/230Vac, cold start |
| Leakage Current |
<1mA at 240Vac |
| Set Up, Rise Time |
500ms, 30ms/230Vac 1000ms, 30ms/115Vac at full load |
| Hold Time |
Typically 50ms/230Vac 20ms/115Vac at full load |
| Over Load Protection |
105 ~ 160% rated output power |
|
Constant current limiting, recovers automatically after fault condition is removed |
| Over Voltage Protection |
Shut down output voltage, re-power on to recover |
| Working Temperature |
-20°C to +70°C (Refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-40°C to +85°C, 10 ~ 95% RH |
| Temperature Coefficient |
±0.03%/°C (0 ~ 50°C) |
| Vibration |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
|
Mounting: Compliance to IEC60068-2-6 |
| Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| Safety Standards |
UL508, TUV EN60950-1 Approved |
| EMC |
Compliance to EN55011; EN55022 (CISPR22) Class B; EN61000-3-2,-3; ENV50204; |
|
EN61000-4-2,3,4,5,6,8,11; EN55024; EN61000-6-1; EN61204-3 Light industry level, criteria A |
| MTBF |
236.9K hrs min. MIL-HDBK-217F (25°C) |