| DC Input/Bus Voltage |
24 ~ 29V |
| Rated Current |
40A |
| Battery Input/Output Voltage |
21 ~ 29V |
| Current Range |
0 ~ 40A |
| Charge Current |
2A |
| External Battery |
4 / 7 / 12AH / 24V |
| Relay Contact Rating |
30VDC, 1A |
| DC Bus OK |
Relay contact : Short when DC voltage between 21~29V(3%), relay contacts ; Green LED on front panel |
|
LED(Green) : DC BUS OK : light, DC BUS fail : dark |
| Battery Fail |
Relay contact: Short when battery failure is observed through the battery test function, |
|
relay contacts; Red LED on front panel LED(Green) : DC BUS OK : light, DC BUS fail : dark |
| Battery Discharge |
Relay contact: Short when battery in discharge condition, relay contacts; |
|
Yellow LED on front panel LED(Green) : DC BUS OK : light, DC BUS fail : dark |
| Working Temperature |
-20°C to +70°C |
| Working Humidity |
20 ~ 90% RH |
| Storage Temperature, Humidity |
-20°C to +85°C, 10 ~ 95% RH |
| Vibration |
Component : 10 ~ 500Hz, 2G 10min./1cycle, 60min. each X,Y, Z axes ; |
|
Mounting : Compliance to IEC600068-2-6 |
| Withstand Voltage |
Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC |
| Isolation Resistance |
Terminal-Chassis :>100M Ohms/500VDC 2570%RH |
| EMC |
Compliance to EN55022 (CISPR22) Class B |
|
EN61000-4-2,3,4,5,6,8, ENV50204, Heavy industry level, criteria A |
| MTBF |
161.9Khrs min. MIL-HDBK-217F (25°C) |