General Specifications
| Input Voltage |
85 ~ 264VAC 120 ~ 370VDC |
| Input Frequency |
47 ~ 63Hz |
| AC Current |
0.88A/115VAC 0.48A/230VAC |
| Inrush Current |
15A/115VAC 30A/230VAC cold start |
| Setup, Rise Time |
100ms, 30ms/230VAC 100ms, 30ms/115VAC at full load |
| Hold Time |
100ms/230VAC 21ms/115VAC at full load |
| Over Load Protection |
105 ~ 160% rated output power |
|
Constant current limiting, recovers automatically after fault condition is removed |
| Over Voltage Protection |
Shut down o/p voltage, re-power on to recover |
| Working Temperature |
-20°C to +60°C (Refer to output load derating curve) |
| Working Humidity |
20% to 90% RH non-condensing |
| Storage Temp., Humidity |
-40°C to +85°C , 10% to 95%RH |
| Temp. Coefficient |
±0.03%/°C (0 to 50°C) |
| Vibration |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes |
| Safety Standards |
UL60950-1, TUV EN60950-1 Approved, Design refer to EN50178 |
| Withstand Voltage |
I/P-O/P:3KVAC |
| Isolation Resistance |
I/P-O/P:100M Ohms/500VDC |
| EMC |
Compliance to EN55011,EN55022 (CISPR22) Class B, EN61000-3-2,-3 |
|
EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-1, EN61204-3 Light industry, Criteria A |
| MTBF |
441.5K hrs min. MIL-HDBK-217F (25°C) |
|