| Input Voltage |
85 ~ 264VAC 120 ~ 370VDC |
| Input Frequency |
47 ~ 63Hz |
| Input Current |
1.5A/115VAC 0.9A/230VAC |
| Inrush Current |
45A cold start |
| Leakage Current |
<2mA/ 240VAC |
| Voltage Adjustment Range |
+15,-5% |
| Line Regulation |
±1.0% |
| Set Up, Rise Time |
500ms, 30ms/230VAC 1200ms, 30ms/115VAC at full load |
| Hold Up Time |
50ms/230VAC 16ms/115VAC at full load |
| Temperature Compensation |
By NTC (not provide with the power supply) |
| Output Voltage Sensor |
L=output voltage +0.7, -0V |
| Over Load Protection |
Hiccup mode, recovers automatically after fault condition is removed |
| Over Voltage Protection |
Shut down o/p voltage, re-power on to recover |
| Working Temperature |
-20°C ~ +60°C (Refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-40°C ~ +85°C, 10 ~ 95% RH |
| Temperature Coefficient |
±0.03%/°C (0 ~ 45°C) |
| Vibration |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes |
| Safety Standards |
UL60950-1, CB (IEC60950-1), CCC GB4943 approved |
| Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH |
| EMC |
Compliance to EN55022 (CISPR22) Class B; EN61000-3-2,-3; EN61000-4-2, 3, 4, 5, 6, 8,11; |
|
ENV50204, EN55024, EN61000-6-1, light industry level, criteria A |
| MTBF |
461.2K hrs min. MIL-HDBK-217F (25°C) |
| Dimensions |
159 x 97 x 38mm |