| Input Voltage |
85 ~ 265Vac 120 ~ 370Vdc |
| Input Frequency |
47 ~ 63Hz |
| Power Factor |
PF> 0.95/230Vac PF> 0.98/115Vac at full load |
| Input Current |
1.3A/115Vac 0.8A/230Vac |
| Inrush Current |
30A/115Vac 60A/230Vac, cold start |
| Leakage Current |
<1mA/240Vac |
| Set Up, Rise Time |
3000ms, 50ms/230Vac 20ms/115Vac at full load |
| Hold Up Time |
50ms/230Vac 20ms/115Vac at full load |
| Over Load Protection |
105 ~ 150% rated output power |
|
Constant current limiting, recovers automatically after fault condition is removed |
| Over Voltage Protection |
Shut down o/p voltage, re-power on to recover |
| Over Temperature Protection |
90°C ±10°C (RTH2) detect on heatsink of power transistor |
|
Shut down o/p voltage, re-power on to recover |
| DC OK Signal |
Relay contact rating (max) 30V/1A resistive |
| Working Temperature |
-10°C ~ +60°C (refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-40°C ~ +85°C, 10 ~ 95% RH |
| Temperature Coefficient |
±0.03%/°C (0 ~ 50°C) |
| Vibration |
Component: 10 ~ 500Hz, 2G 10min./ 1 cycle, period for 60min. each along X, Y, Z axes; |
|
Mounting: Compliance to IEC60068-2-6 |
| Withstand Voltage |
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG: >100M Ohms/500VDC 25°C 70%RH |
| Safety Standards |
UL508, TUV EN60950-1 Approved. Design refers to NEC CLASS 2 (for 24V & 48V only) |
| EMC |
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B; EN61000-3-2,-3; ENV50204; |
|
EN61000-4-2, 3, 4, 5, 6, 8, 11; EN55024; EN61000-6-2; EN61204-3, heavy industry level, criteria A |
| MTBF |
346K hrs min. MIL-HDBK-217F (25°C) |