| Input Voltage Range |
88 ~ 264Vac 124 ~ 370Vdc |
| Input Frequency |
47 ~ 63Hz |
| Input Current |
3A/115Vac 1.6A/230Vac |
| Inrush Current |
30A/115Vac 45A/230Vac, cold start |
| Set Up, Rise Time |
2700ms, 80ms/230Vac 2700ms, 80ms/115Vac at full load |
| Over Load Protection |
105 ~ 135% rated output power |
|
Constant current limiting, recovers automatically after fault condition is removed |
| Over Voltage Protection |
Shut down o/p voltage, re-power on to recover |
| Over Temperature Protection |
90°C ±15°C (RTH2) detect on heatsink of power transistor |
|
Shut down o/p voltage, re-power on to recover |
| Working Temperature |
-20°C ~ +60°C (Refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-40°C ~ +85°C , 10 ~ 95% RH |
| Temperature Coefficient |
±0.03%/°C (0 ~ 50°C) |
| Vibration |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,Y, Z axes; |
|
Mounting: Compliance to IEC60068-2-6 |
| Withstand Voltage |
I/P-O/P:3KVAC |
| Isolation Resistance |
I/P-O/P:>100M Ohms/500VDC 25°C 70% RH |
| Safety Standards |
UL60950-1,TUV EN60950-1 Approved, Design refers to EN50178 |
| EMC |
Compliance to EN61204-3; EN61000-3-2,-3; EN55024; |
|
EN61000-4-2, 3, 4, 5, 6, 8, 11; EN55024; EN61000-6-2; EN61204-3, heavy industry level, criteria A |
| MTBF |
486K hrs min. MIL-HDBK-217F (25°C) |