DR-100 Series - 100W Single Output Class II DIN Rail Power Supply
Home > Products >Din Rail > 100W Single Output Class II DIN Rail Power Supply
Features- Universal AC input
- Short circuit, over load, over voltage, over temperature protections
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- Isolation class II
- LED indicator for power on
- No load power consumption<1W
- 100% full load burn-in test
Applications- Building automation
- Security
- Datacommunications
- IT
- Control Panels
DescriptionDR-100 Series is a Class II switching power supply. Designed with a fully isolated plastic case to prevent user contact and the risk of shock. Other standard features include its low no load power consumption, to save energy, short circuit, over load, over voltage and over temperature protections.
|
Standards
  
|
Case Details
100 x 56 x 93mm
|
Specification
| Input Voltage Range |
88 ~ 264Vac 124 ~ 370Vdc |
| Input Frequency |
47 ~ 63Hz |
| Input Current |
3A/115Vac 1.6A/230Vac |
| Inrush Current |
30A/115Vac 45A/230Vac, cold start |
| Set Up, Rise Time |
2700ms, 80ms/230Vac 2700ms, 80ms/115Vac at full load |
| Over Load Protection |
105 ~ 135% rated output power |
|
Constant current limiting, recovers automatically after fault condition is removed |
| Over Voltage Protection |
Shut down o/p voltage, re-power on to recover |
| Over Temperature Protection |
90°C ±15°C (RTH2) detect on heatsink of power transistor |
|
Shut down o/p voltage, re-power on to recover |
| Working Temperature |
-20°C ~ +60°C (Refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-40°C ~ +85°C , 10 ~ 95% RH |
| Temperature Coefficient |
±0.03%/°C (0 ~ 50°C) |
| Vibration |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,Y, Z axes; |
|
Mounting: Compliance to IEC60068-2-6 |
| Withstand Voltage |
I/P-O/P:3KVAC |
| Isolation Resistance |
I/P-O/P:>100M Ohms/500VDC 25°C 70% RH |
| Safety Standards |
UL60950-1,TUV EN60950-1 Approved, Design refers to EN50178 |
| EMC |
Compliance to EN61204-3; EN61000-3-2,-3; EN55024; |
|
EN61000-4-2, 3, 4, 5, 6, 8, 11; EN55024; EN61000-6-2; EN61204-3, heavy industry level, criteria A |
| MTBF |
486K hrs min. MIL-HDBK-217F (25°C) |
|
Items
DR-100 Series Output Data
|
Part Code
|
Voltage
|
Rated Current
|
Current Range
|
Rated Pwr
|
R&N
|
Volt. Adj.
|
Tol.
|
Line Reg.
|
Load Reg.
|
Eff.
|
OVP
|
|
DR-100-12
|
12V
|
7.5A
|
0 ~ 7.5A
|
90W
|
120mV
|
12 ~ 15V
|
±2.0%
|
±1.0%
|
±1.0%
|
87%
|
16 ~ 20V
|
|
DR-100-15
|
15V
|
6.5A
|
0 ~ 6.5A
|
97.5W
|
120mV
|
15 ~ 18V
|
±1.0%
|
±1.0%
|
±1.0%
|
87%
|
19 ~ 23V
|
|
DR-100-24
|
24V
|
4.2A
|
0 ~ 4.2A
|
100.8W
|
150mV
|
24 ~ 29V
|
±1.0%
|
±1.0%
|
±1.0%
|
89%
|
30 ~ 35V
|
|
(258KB)
|