| RACK SYSTEM SPECIFICATION |
|
| Input Voltage |
90 ~ 264Vac 127 ~ 370Vdc |
| Input Frequency |
47 ~ 63Hz |
| Leakage Current |
<3.5mA/ 230Vac |
| Auxiliary Power |
5V @ 0.3A |
| Remote On/Off Control |
By electrical signal or dry contact ON:short OFF:open |
| Remote Sense |
Compensate voltage drop on the load wiring up to 0.5V |
|
Local Sense should be connected in order to get the correct output voltage |
|
if the Remote Sense is not used |
| DC OK Signal |
Open collector signal, on when Vout >80% ±5%, max. sink current:10mA |
| AC Fail Signal |
Open collector signal, refer to function manual |
| Output Voltage Trim |
Adjustment of output voltage, possible between 90 ~ 110% of rated output |
| Over Temperature Warning |
Logic High for over temperature warning, refer to function manual |
| Working Temperature |
-20°C to +60°C (Refer to output load derating curve) |
| Working Humidity |
20 ~ 90% RH non-condensing |
| Storage Temperature, Humidity |
-40°C to +85°C, 10 ~ 95% RH |
| Temperature Coefficient |
±0.02%/°C (0 ~ 50°C) |
| Vibration |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,Y, Z axes |
| Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| Safety Standards |
UL60950-1,TUV EN60950-1 Approved |
| EMC |
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3, |
|
EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A |