| Input Voltage |
Three-Phase 340 to 550VAC |
| Input Frequency |
47 ~ 63Hz |
| AC Current (Typ.) |
2A/400VAC 1.6A/500VAC |
| Inrush Current (max.) |
50A cold start |
| Leakage Current |
<3.5mA / 530VAC |
| Setup, Rise Time |
200ms, 60ms/400VAC 200ms, 60ms/500VAC at full load |
| Hold Time (Typ.) |
14ms/400VAC 30ms/500VAC at full load |
| Over Load Protection |
105 ~ 125% rated output power |
|
Constant current limiting, unit will shut down o/p voltage after 3 sec., re-power on to recover |
| Over Voltage Protection |
Shut down output voltage, re-power on to recover |
| Over Temperature Protection |
110°C ±5°C (TSW1) Detect on heatsink of power transistor |
|
85°C ±5°C (TSW2) Detect on heatsink of power diode |
|
Shut down o/p voltage, recovers automatically after temperature goes down |
| Working Temperature |
-20°C to +60°C (Refer to output load derating curve) |
| Working Humidity |
20% to 90% RH non-condensing |
| Storage Temperature, Humidity |
-40°C to +85°C, 10% to 95% RH |
| Temperature Coefficient |
±0.03%/°C (0 ~ 50°C) |
| Vibration |
Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; |
|
Mounting: Compliance to IEC60068-2-6 |
| Safety Standards |
UL508, UL60950-1, TUV EN60950-1 Approved |
| Withstand Voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| EMI Conduction & Radiation |
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B |
| Harmonic Current |
Compliance to EN61000-3-2,-3 |
| EMS Immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2) Heavy industry |
| MTBF |
122.5Khrs min. MIL-HDBK-217F (25?C) |
| Dimensions |
276 x 125.2 x 100mm |