Sunpower security

Door Entry Power Supplies for Access Control Systems

Reliable power is essential for the safe and dependable operation of modern door entry and access control systems. From a single entrance in a small office to multi-door installations in apartment buildings, commercial premises and industrial facilities, the power supply supports the equipment responsible for controlling access and managing building security.

Modern door entry systems often combine electronic locks, intercoms, card readers, keypads, video entry equipment and central access controllers. Each component may have different electrical requirements, making power supply selection an important consideration during system design.

Sunpower Electronics supports door entry and access control applications with power conversion solutions suited to different voltage requirements, installation environments and backup power needs. Understanding how these systems operate, particularly during mains failures and emergency conditions, is essential when selecting a suitable power supply.


Why Reliable Power Matters in Door Entry Systems

Electronic access control systems are designed to manage who can enter a building or restricted area. Depending on the installation, they may also record access activity, communicate with building management systems and coordinate with other security equipment.

Power interruptions can affect several parts of an access control installation, including electronic locking devices, credential readers, communication equipment and door controllers.

The consequences depend on the design of the system. Some doors may automatically unlock when power is removed, while others may remain locked against entry but retain a mechanical means of escape.

A suitable door entry power supply must therefore support the electrical requirements of the equipment while remaining compatible with the building's security, emergency access and escape arrangements.

Important considerations include:

  • Stable output voltage: Providing a regulated supply within the operating limits of connected equipment.

  • Adequate power capacity: Supporting electronic locks, readers, controllers, intercoms and other connected devices.

  • Electrical protection: Incorporating suitable safeguards against overload, short circuits and other electrical faults.

  • Power continuity: Supporting battery-backed operation where essential functions must continue during mains interruptions.

  • System monitoring: Providing status information, where available, to help identify power failures or battery-related faults.

  • Safety requirements: Ensuring the power architecture does not compromise the building's emergency escape arrangements.

Selecting the right power supply requires an understanding of both the electrical load and the way the door must behave during normal and abnormal operating conditions.


Understanding Door Entry and Access Control Power Requirements

Door entry systems can vary considerably in their complexity.

A basic installation may contain a single electric strike, keypad and access controller. A larger commercial building might have multiple controlled doors, video intercoms, electronic locking systems and centralised security management equipment.

These systems commonly use low-voltage electrical supplies, including 12V DC and 24V DC, although some devices require other voltages or AC inputs.

The correct supply must always be selected according to the manufacturer's specifications.


Electronic Locks and Door Releases

Electronic locking devices are among the most important electrical loads in an access control system.


Common examples include:

Electromagnetic locks

Often referred to as maglocks, electromagnetic locks use magnetic force to secure a door. Many conventional maglocks require continuous electrical power to maintain the locking force and release when power is removed.


Electric strikes

Electric strikes control the release of a door latch. Depending on the design, they may require power to release the latch or power to maintain a particular locked condition.


Electromechanical locks

These combine electrical operation with mechanical locking components and may be designed for different operating and emergency-release arrangements.

The power supply must accommodate the lock's voltage and current requirements, including any relevant activation current, operating duration and duty-cycle limitations.

It is also important to determine how the locking mechanism behaves when power is lost.


Intercoms, Keypads and Access Readers

Modern door entry systems frequently incorporate equipment that allows visitors or authorised users to request access.

This can include:

  • Audio and video intercoms

  • RFID and proximity card readers

  • Key fob access systems

  • PIN code keypads

  • Biometric identification equipment

  • Network-connected door controllers

  • Remote access and monitoring equipment

Some devices operate from dedicated DC supplies, while compatible IP-based equipment may use Power over Ethernet (PoE).

The overall power architecture must account for the electrical requirements of each connected device, including communication equipment needed for remote operation.


Choosing Between 12V and 24V Door Entry Power Supplies

Selecting the correct output voltage is one of the first steps in specifying a door entry PSU.

Both 12V DC and 24V DC are commonly encountered in electronic access control equipment, but they are not interchangeable unless the connected devices are explicitly designed to support both.

A 12V lock must not be connected to a 24V output unless its manufacturer specifies that the device is compatible with that voltage.

For installations with several devices, the designer should identify whether the equipment can share a common supply voltage or whether separate power outputs or conversion stages are required.


The relationship between voltage, current and power is expressed as:

Power (W) = Voltage (V) × Current (A)


For example, a 24V DC device drawing 0.5A consumes:

24V × 0.5A = 12W


If several compatible devices operate from the same power supply, their simultaneous electrical demands must be combined when calculating the required output capacity.

For longer cable runs, conductor resistance and voltage drop must also be considered.

Where two devices require the same amount of power, the higher-voltage option generally draws less current, which can reduce resistive losses when otherwise comparable cabling is used.

However, the correct voltage is ultimately determined by the connected equipment, not by distribution efficiency alone.


Calculating the Power Requirements of an Access Control System

A door entry PSU should be sized according to the maximum expected electrical demand of the connected equipment.

Consider an illustrative 24V DC installation containing:

EquipmentPower requirement
Electromagnetic lock
6W
Access controller8W
Card reader4W
Video intercom12W
Total connected load30W

In this example, the total continuous load would be 30W if all devices operate simultaneously at their stated power requirements.

The corresponding current would be:

30W ÷ 24V = 1.25A

This is the calculated operating load, not necessarily the required PSU rating.

The designer must also consider:

  • Maximum simultaneous loading

  • Lock activation or start-up currents

  • Additional connected devices

  • Cable voltage drop

  • Temperature-related power derating

  • Battery charging demand, where supported

  • An appropriate design margin

The final power supply must be capable of supporting the required load under the actual operating conditions.

Where a PSU incorporates battery charging, the manufacturer's output ratings should also be checked to establish how much power is available for the connected load while the battery is charging.


Fail-Safe and Fail-Secure Door Locking

One of the most important aspects of access control system design is understanding how a door behaves when electrical power is interrupted.

Electronic locking devices are commonly described as fail-safe or fail-secure, although the exact operating behaviour depends on the device and the complete door assembly.


Fail-Safe Locking

A fail-safe locking device releases when its electrical power is removed.

This arrangement is commonly associated with electromagnetic locks and may be used where the door's escape strategy requires electrical locking to release on power failure.

However, fail-safe operation alone does not establish that the complete door installation is compliant with fire safety or emergency escape requirements.

The door hardware, release controls, fire alarm interface and building's escape strategy must all be considered.


Fail-Secure Locking

A fail-secure locking device remains secured against unauthorised entry when electrical power is removed.

This can be useful where maintaining security during a power interruption is important.

However, fail-secure locking must not prevent safe escape from an occupied building.

Depending on the application, a door may use mechanical escape hardware that allows occupants to leave without relying on electrical power.

The distinction between controlling entry and allowing escape is essential.

A power supply or battery backup arrangement must never be used to maintain a locked condition that conflicts with the building's required means of escape.

The appropriate locking configuration should be established by competent access control and fire safety professionals based on the building's use, door function and applicable requirements.


Battery Backup for Door Entry and Access Control Systems

Some access control installations require continued operation during a mains power failure.

Battery-backed power supplies and DC uninterruptible power systems can help support equipment such as access controllers, intercoms, readers and suitable locking devices.

Depending on the system design, this may allow authorised access, communication or monitoring functions to continue when the primary power source is unavailable.

However, backup power requirements depend on how the doors must behave during a power failure.

For example, an electronic locking device that must release when power is removed may require a different safety and control arrangement from equipment intended to remain operational through a battery supply.


Calculating Battery Backup Runtime

The required battery capacity depends on the total connected load, desired operating time and available battery energy.

As a basic illustration, consider a door entry system consuming 40W continuously.


If the design requires three hours of backup operation:

40W × 3 hours = 120Wh

This represents the energy required by the connected equipment.


If a nominal 24V battery system is used, the ideal equivalent capacity would be:

120Wh ÷ 24V = 5Ah

This is only a theoretical starting point.


In practice, the battery arrangement must account for:

  • Usable battery capacity

  • Battery discharge characteristics

  • Charging and conversion losses

  • Battery ageing and temperature

  • End-of-discharge voltage limits

  • Required operating time and load variation

Battery sizing must also follow the relevant equipment manufacturer's instructions and the applicable system requirements.

A battery's stated ampere-hour rating does not, by itself, guarantee a particular backup duration.


Power Supply Monitoring and Status Signals

Some battery-backed power supplies provide monitoring and status functions to support maintenance and fault identification.

Depending on the model, these may include:

  • AC OK indication

  • DC output status

  • Battery low indication

  • Battery fault or charging status

  • Remote alarm contacts

These features can help installers and building operators identify abnormal operating conditions before they result in loss of service.

For larger installations, monitoring may form part of an integrated security or building management system.


Fire Safety and Emergency Escape Considerations

Access control systems often operate alongside fire detection, alarm and emergency escape arrangements.

The power supply is only one component of the wider system, but its behaviour during faults and power interruptions can affect the operation of electronically controlled doors.

The requirements depend on whether the door forms part of an escape route, the type of locking equipment installed and the building's fire and evacuation strategy.

Relevant UK standards and guidance may include:


BS 7273-4

Provides guidance relating to the actuation of release mechanisms for doors, including relevant interfaces with fire detection and fire alarm systems.


BS EN 179 and BS EN 1125

Address emergency exit devices and panic exit devices operated by mechanical means, as applicable to the relevant door and building use.


BS EN 13637

Covers electrically controlled exit systems intended for use on escape routes.


These standards relate to different aspects of the complete door and access control installation. They should not be treated as interchangeable product approvals.

Where electronic locking is used on an escape route, the arrangement must support the required safe means of escape.

Fire alarm interfaces, manual release arrangements and behaviour during mains or system faults must be evaluated as part of the complete design.


Power Supply Safety Standards

The electrical safety standard applicable to a door entry power supply depends on the product's design, intended application and regulatory scope.

For example, BS EN IEC 62368-1 may be relevant to certain power supplies associated with audio, video and information technology equipment.

EN 54-4 applies to power supply equipment within its defined scope for fire detection and fire alarm systems. It is not a general approval requirement for every door entry PSU.

Engineers and installers should therefore verify the specific approvals and declarations applicable to each product rather than assuming that all access control power supplies require the same certification.


Outdoor Door Entry Power Supplies and Environmental Protection

Door entry equipment is frequently installed at external building entrances, gates, industrial sites and exposed access points.

These locations may subject electrical equipment to moisture, dust, temperature fluctuations and other environmental stresses.

The power supply and associated equipment must be protected appropriately for the installation conditions.


Ingress Protection Ratings

Ingress Protection (IP) ratings describe the protection provided by an enclosure against access, solid foreign objects and water ingress under specified test conditions.

For example:

  • IP20: Provides protection against access by a standard test finger and solid objects of 12.5mm or larger, but no rated protection against water ingress.

  • IP65: Dust-tight protection and protection against water jets.

  • IP67: Dust-tight protection and protection against temporary immersion under defined conditions.

A higher IP rating does not automatically make a product suitable for every outdoor application.

The installation must account for the type and duration of environmental exposure, as well as cable entries, connectors, mounting arrangements and enclosure integrity.

An indoor-rated power supply may be suitable when installed inside a correctly specified protective enclosure, provided thermal management and other installation requirements are satisfied.


Temperature and Cooling

Enclosed external installations may experience elevated temperatures caused by solar exposure and heat generated by electrical equipment.

Power supplies must be capable of delivering the required load across the expected operating temperature range.

Where a PSU is installed inside a cabinet, designers should review cooling requirements, installation clearances and any applicable power derating.

Fanless power supplies can reduce reliance on mechanical cooling components, although they still require adequate heat dissipation.


Choosing the Right Door Entry Power Supply

Selecting a power supply for door entry and access control equipment requires consideration of both electrical performance and the wider security system.

Before specifying a PSU, engineers and installers should assess the following factors.


1. Output Voltage

Confirm the voltage requirements of electronic locks, intercoms, controllers and access readers.


2. Total Power Demand

Calculate the maximum simultaneous load, including any start-up or activation current requirements.


3. Installation Format

Determine whether the application requires an enclosed PSU, DIN rail power supply, external adapter or integrated battery-backed solution.


4. Locking Behaviour

Identify whether the connected locking devices are fail-safe or fail-secure, and ensure that their operation is compatible with the required escape and security arrangements.


5. Battery Backup

Determine which equipment must remain operational during a mains failure, how long it must operate and how the backup system will interact with door-release functions.


6. Monitoring and Protection

Assess the need for electrical fault protection, AC OK indication, battery monitoring and remote status signalling.


7. Environmental Requirements

Consider operating temperature, moisture, dust, installation location and enclosure protection.


8. Safety and Compliance

Confirm the applicable product standards and ensure the complete access control installation meets the building's relevant safety and escape requirements.


9. Maintenance and Expansion

Consider accessibility, battery replacement, additional doors and future changes to the access control system.


By evaluating these requirements early, engineers can select a power solution that supports dependable operation without compromising the intended function of the complete system.


Supporting Reliable Door Entry and Access Control Systems

From small commercial premises to multi-door residential and industrial installations, reliable power conversion is essential for dependable door entry and access control operation.

The correct power supply must support the electrical requirements of connected equipment while accounting for backup power, environmental protection and the system's security and emergency escape functions.

Sunpower Electronics supports engineers, OEMs and system integrators in identifying suitable power conversion solutions for door entry, intercom and electronic access control applications.

With access to AC/DC power supplies, industrial power conversion technologies and battery charging solutions, Sunpower can help customers assess suitable options based on their voltage, load, installation and operational requirements.

Contact the Sunpower Electronics technical team to discuss your door entry and access control power supply requirements.



Recommended for you

Designing Power Systems with Confidence from the Outset

Designing Power Systems with Confidence from the Outset

Learn how to select the right power supply from design to production, covering power requirements, efficiency, thermal management, compliance and reliability.
DC-DC Converters in Electrified DC Grids

DC-DC Converters in Electrified DC Grids

Discover how DC-DC converters support electrified DC grids, industrial automation and energy storage through efficient voltage conversion and power distribution.
Reliable Power in Harsh Environments

Reliable Power in Harsh Environments

Discover how to select reliable power supplies for harsh environments, including extreme temperatures, dust, moisture, vibration and industrial applications.
CCTV Power Supplies for Security and Surveillance Systems

CCTV Power Supplies for Security and Surveillance Systems

Explore CCTV power supply solutions for security cameras and surveillance systems, including AC/DC power conversion, outdoor installations and battery backup.

Speak to a technical expert!

Have a question or request? Click below to contact us, and our team will be happy to help.

Contact us